Wire size calculator
Enter the breaker size and how far the wire runs. You get the smallest copper NM-B, copper THHN and aluminum wire that meets the NEC ampacity table and keeps voltage drop under 3%.
Wire size by breaker (short runs)
| Breaker | Copper NM-B | Copper THHN | Aluminum |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 25 A | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 35 A | 8 AWG | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 45 A | 6 AWG | 8 AWG | 6 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 2 AWG | 4 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 2 AWG |
| 100 A | — | 3 AWG | 1 AWG |
| 110 A | — | 2 AWG | 1/0 AWG |
| 125 A | — | 1 AWG | 2/0 AWG |
| 150 A | — | 1/0 AWG | 3/0 AWG |
| 175 A | — | 2/0 AWG | 4/0 AWG |
| 200 A | — | 3/0 AWG | 250 kcmil |
Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.
EV charger circuits
16 A charger24 A charger32 A charger40 A charger48 A charger
How we size the wire
First we find the smallest wire whose NEC 2023 Table 310.16 ampacity is at least the breaker size, applying the 240.4(D) limits on 14, 12 and 10 AWG. Then we check voltage drop with the wire’s resistance from Chapter 9 Table 8 and move up a size until the drop is 3% or less, the level the NEC recommends for branch circuits.