CircuitSizer

Wire size calculator

Enter the breaker size and how far the wire runs. You get the smallest copper NM-B, copper THHN and aluminum wire that meets the NEC ampacity table and keeps voltage drop under 3%.

Wire size by breaker (short runs)

BreakerCopper NM-BCopper THHNAluminum
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
25 A10 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG
35 A8 AWG8 AWG8 AWG
40 A8 AWG8 AWG8 AWG
45 A6 AWG8 AWG6 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A2 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A—3 AWG1 AWG
110 A—2 AWG1/0 AWG
125 A—1 AWG2/0 AWG
150 A—1/0 AWG3/0 AWG
175 A—2/0 AWG4/0 AWG
200 A—3/0 AWG250 kcmil

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

EV charger circuits

How we size the wire

First we find the smallest wire whose NEC 2023 Table 310.16 ampacity is at least the breaker size, applying the 240.4(D) limits on 14, 12 and 10 AWG. Then we check voltage drop with the wire’s resistance from Chapter 9 Table 8 and move up a size until the drop is 3% or less, the level the NEC recommends for branch circuits.