What size wire for a 15 amp breaker?

For a 15 amp breaker on a short run, use 14 AWG copper THHN in conduit, 14 AWG copper NM-B (Romex) or 12 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 14 AWG THHN wire ↗ Shop 14 AWG NM-B cable ↗

Wire size by distance at 240 volts

15 A breaker at 240 V, 12 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft14 AWG14 AWG12 AWG
50 ft14 AWG14 AWG12 AWG
75 ft14 AWG14 AWG12 AWG
100 ft12 AWG12 AWG10 AWG
125 ft12 AWG12 AWG10 AWG
150 ft12 AWG12 AWG8 AWG
200 ft10 AWG10 AWG8 AWG
250 ft8 AWG8 AWG6 AWG
300 ft8 AWG8 AWG6 AWG

15 amp circuit at 120 volts

15 A breaker at 120 V, 12 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft14 AWG14 AWG12 AWG
50 ft12 AWG12 AWG10 AWG
75 ft12 AWG12 AWG8 AWG
100 ft10 AWG10 AWG8 AWG
125 ft8 AWG8 AWG6 AWG
150 ft8 AWG8 AWG6 AWG
200 ft6 AWG6 AWG4 AWG
250 ft6 AWG6 AWG4 AWG
300 ft6 AWG6 AWG3 AWG

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.