What size wire for a 15 amp breaker?
For a 15 amp breaker on a short run, use 14 AWG copper THHN in conduit, 14 AWG copper NM-B (Romex) or 12 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.
Shop 14 AWG THHN wire ↗ Shop 14 AWG NM-B cable ↗
Wire size by distance at 240 volts
| One-way distance | Copper NM-B | Copper THHN | Aluminum |
|---|---|---|---|
| 25 ft | 14 AWG | 14 AWG | 12 AWG |
| 50 ft | 14 AWG | 14 AWG | 12 AWG |
| 75 ft | 14 AWG | 14 AWG | 12 AWG |
| 100 ft | 12 AWG | 12 AWG | 10 AWG |
| 125 ft | 12 AWG | 12 AWG | 10 AWG |
| 150 ft | 12 AWG | 12 AWG | 8 AWG |
| 200 ft | 10 AWG | 10 AWG | 8 AWG |
| 250 ft | 8 AWG | 8 AWG | 6 AWG |
| 300 ft | 8 AWG | 8 AWG | 6 AWG |
15 amp circuit at 120 volts
| One-way distance | Copper NM-B | Copper THHN | Aluminum |
|---|---|---|---|
| 25 ft | 14 AWG | 14 AWG | 12 AWG |
| 50 ft | 12 AWG | 12 AWG | 10 AWG |
| 75 ft | 12 AWG | 12 AWG | 8 AWG |
| 100 ft | 10 AWG | 10 AWG | 8 AWG |
| 125 ft | 8 AWG | 8 AWG | 6 AWG |
| 150 ft | 8 AWG | 8 AWG | 6 AWG |
| 200 ft | 6 AWG | 6 AWG | 4 AWG |
| 250 ft | 6 AWG | 6 AWG | 4 AWG |
| 300 ft | 6 AWG | 6 AWG | 3 AWG |
Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.
Check your own circuit
Other breaker sizes
20 A25 A30 A35 A40 A45 A50 A60 A70 A80 A90 A100 A110 A125 A150 A175 A200 A
EV chargers
16 A charger24 A charger32 A charger40 A charger48 A charger