What size wire for a 125 amp breaker?
For a 125 amp breaker on a short run, use 1 AWG copper THHN in conduit, no NM-B cable (it isn’t made that large) or 2/0 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.
Wire size by distance at 240 volts
| One-way distance | Copper NM-B | Copper THHN | Aluminum |
|---|---|---|---|
| 25 ft | — | 1 AWG | 2/0 AWG |
| 50 ft | — | 1 AWG | 2/0 AWG |
| 75 ft | — | 1 AWG | 2/0 AWG |
| 100 ft | — | 1 AWG | 2/0 AWG |
| 125 ft | — | 1 AWG | 2/0 AWG |
| 150 ft | — | 1 AWG | 2/0 AWG |
| 200 ft | — | 1 AWG | 2/0 AWG |
| 250 ft | — | 1/0 AWG | 3/0 AWG |
| 300 ft | — | 2/0 AWG | 4/0 AWG |
Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.
Check your own circuit
Can I use 2 AWG on a 125 amp breaker?
No. 2 AWG copper is too small: it is rated 115 A at 75 °C, which is less than 125 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.