What size wire for a 110 amp breaker?

For a 110 amp breaker on a short run, use 2 AWG copper THHN in conduit, no NM-B cable (it isn’t made that large) or 1/0 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 2 AWG THHN wire ↗

Wire size by distance at 240 volts

110 A breaker at 240 V, 88 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft—2 AWG1/0 AWG
50 ft—2 AWG1/0 AWG
75 ft—2 AWG1/0 AWG
100 ft—2 AWG1/0 AWG
125 ft—2 AWG1/0 AWG
150 ft—2 AWG1/0 AWG
200 ft—2 AWG1/0 AWG
250 ft—1 AWG2/0 AWG
300 ft—1/0 AWG3/0 AWG

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 3 AWG on a 110 amp breaker?

No. 3 AWG copper is too small: it is rated 100 A at 75 °C, which is less than 110 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.